Cummins
DIY-C94B
94kVA/75kW
85kVA/68kW
N/A
50-1500RPM
Cummins 6BT5.9-G2
T2
Leroy-Somer TAL-A44-C
| Availability: | |
|---|---|
| Quantity: | |
| Frequency | 50Hz | 60Hz |
| Voltage-Phases*1 | 400V/ 3Phases | 220V/3Phases |
| Power Factor | 0.8 | 0.8 |
| Standby Power(ESP)*2 | 94kVA/75kW | 108kVA/86kw |
| Prime Power(PRP)*3 | 85kVA/68kW | 98kVA/78kw |
| Continuous Power(COP)*4 | N/A | N/A |
| Max Current | 136Amps | 283Amps |
| Structure Type | Open Frame | Soundproof Canopy |
| Dimension L*W*H (mm) | 2150*930*1560mm | 2900*1080*2000mm |
| Weight (kgs) | 1180kgs | 1860kgs |
| Sound Pressure Level: dB(A) | 80dB(A)/7meter @ 75%Load | 70dB(A)/7meter @ 75%Load |
| Fuel Tank Capacity (Litres) | 210L | 280L |
| Automatic Run Time | 11 Hours @ 75% Load, 8 Hours @ 100% Load | |
| Engine Brand(Manufacturer) | DCEC Cummins | |
| Engine Model | 6BT5.9-G2 | |
| Aspiration Type | Turbocharged | |
| Engine Type | 6-Stroke Diesel | |
| Number of cylinders | 6 cylinders in Line | |
| Bore and Stroke | 102*120 mm | |
| Displacement | 5.9 L | |
| Compression Ratio | 17.3:1 | |
| Fuel Injection System | BYC PB Direct Injection | |
| Engine Emission: | T2 | |
| Starting System | Cranking Motor-24V | |
| Speed Governor System | Electronic Governor | |
| Speed | 1500RPM | 1800RPM |
| Gross Engine Standby Power | 106kW | 127kw |
| Gross Engine Prime Power | 96kW | 115kw |
| Gross Engine Continuous Power | N/A | N/A |
| Fuel Consumption@Stdby Power | 209g/kW.h | 218g/kW.h |
| Fuel Consumption@Prime Power | 208g/kW.h | 213g/kW.h |
| Fuel Consumption@75% Power | 208g/kW.h | 212g/kW.h |
| Alternator Brand(Manufacturer) | Leroy-Somer | |
| Alternator Model | TAL A44-C | |
| Power Ratings (PF=0.8) | 50Hz at 400V*5 | 60Hz at 220V*6 |
| Continuous Power (H:125/40°C) | 85kVA/68kW | 81kVA/64.8kW |
| Standby Power (H:163/27°C) | 93.5kVA/74.8kW | 102kVA/81.6kW |
| Poles Numbers | 4 | |
| Winding Leads | 6/12 | |
| Connection Type | Y (Star) | |
| Winding Pitch | 2/3 | |
| Insulation Class | H | |
| IP Class(Protection) | IP23 | |
| Waveform: NEMA = TIF | < 50 | |
| Waveform : I.E.C. : THF | < 2 % | |
| AVR Type | R120 (Standard) | R180 (Optional) |
| AVR Voltage Regulation | ± 1 % | ± 0.5 % |
| Excitation System | SHUNT | AREP+/PMG (Optional) |
| Short-circuit Current | 2.7 In: 10 seconds | |
| Control System | Auto-Start 1001 | AMF 2001 |
| Generator Voltages | ● | ● |
| Generator Currents | ● | ● |
| Generator Frequency | ● | ● |
| Generator Apparent power (Kva) | ● | ● |
| Generator Active power (Kw) | ● | ● |
| Generator Reactive power (kVAr) | ● | ● |
| Generator Power factor | ● | ● |
| Engine Speed RPM | ● | ● |
| Engine Coolant temperature | ● | ● |
| Engine Oil pressure | ● | ● |
| Fuel level (%) | ● | ● |
| Battery voltage | ● | ● |
| Battery charge alternator voltage | ● | ● |
| High/Low Voltage Protection | ● | ● |
| High/Low Frequency Protection | ● | ● |
| Over Load Protection | ● | ● |
| Short-circuit Proteciion | ● | ● |
| Over Speed Protection | ● | ● |
| High Coolant Temp. Protection | ● | ● |
| Low Oil Pressure Protection | ● | ● |
| High/Low Battery Voltage Protection | ● | ● |
| Total Running Hours Counter | ● | ● |
| Total Starting Times Counter | ● | ● |
| Total Power kWh | ● | ● |
| Total Power kWArh | ● | ● |
| Cummunications by RS232/485 | ● | ● |
| Remote Monitor by PC Software | ● | ● |
| Remote Start | ● | ● |
| Auto Mains Failure Start | ● | |
| Mains Voltages | ● | |
| Mains Frequency | ● |