Cummins
DIY-C80
80kVA/64kW
73kVA/58kW
N/A
50-1500RPM
Cummins 4BTA3.9G-11
China State II
Leroy-Somer TAL-A44-C
Availability: | |
---|---|
Quantity: | |
Frequency | 50Hz | 60Hz |
Voltage-Phases*1 | 400V/ 3Phases | 220V/ 3Phases |
Power Factor | 0.8 | 0.8 |
Standby Power(ESP)*2 | 80kVA/64kW | 83kVA/66kW |
Prime Power(PRP)*3 | 73kVA/58kW | 75kVA/60kW |
Continuous Power(COP)*4 | N/A | N/A |
Max Current | 115Amps | 218Amps |
Structure Type | Open Frame | Soundproof Canopy |
Dimension L*W*H (mm) | 1900*930*1500mm | 1900*930*1500mm |
Weight (kgs) | 940kgs | 1500kgs |
Sound Pressure Level: dB(A) | 80dB(A)/7meter @ 75%Load | 70dB(A)/7meter @ 75%Load |
Fuel Tank Capacity (Litres) | 160L | 240L |
Automatic Run Time | 11 Hours @ 75% Load, 8 Hours @ 100% Load |
Engine Brand(Manufacturer) | DCEC Cummins | |
Engine Model | 4BTA3.9G-11 | |
Aspiration Type | Turbocharged | |
Engine Type | 4-Stroke Diesel | |
Number of cylinders | 4 cylinders in Line | |
Bore and Stroke | 102*120 mm | |
Displacement | 3.9 L | |
Compression Ratio | 17.3:1 | |
Fuel Injection System | BYC A Direct Injection | |
Engine Emission: | China State II | |
Starting System | Cranking Motor-24V | |
Speed Governor System | Electronic Governor | |
Speed | 1500RPM | 1800RPM |
Gross Engine Standby Power | 80kW | 90kW |
Gross Engine Prime Power | 70kW | 80kW |
Gross Engine Continuous Power | N/A | N/A |
Fuel Consumption@Stdby Power | 206g/kW.h | 206g/kW.h |
Fuel Consumption@Prime Power | 208g/kW.h | 207g/kW.h |
Fuel Consumption@75% Power | 208g/kW.h | 210g/kW.h |
Alternator Brand(Manufacturer) | Leroy-Somer | |
Alternator Model | TAL A44-C | |
Power Ratings (PF=0.8) | 50Hz at 400V*5 | 60Hz at 220V*6 |
Continuous Power (H:125/40°C) | 85kVA/68kW | 81kVA/64.8kW |
Standby Power (H:163/27°C) | 93.5kVA/74.8kW | 102kVA/81.6kW |
Poles Numbers | 4 | |
Winding Leads | 6/12 | |
Connection Type | Y (Star) | |
Winding Pitch | 2/3 | |
Insulation Class | H | |
IP Class(Protection) | IP23 | |
Waveform: NEMA = TIF | < 50 | |
Waveform : I.E.C. : THF | < 2 % | |
AVR Type | R120 (Standard) | R180 (Optional) |
AVR Voltage Regulation | ± 1 % | ± 0.5 % |
Excitation System | SHUNT | AREP+/PMG (Optional) |
Short-circuit Current | 2.7 In: 10 seconds |
Control System | Auto-Start 1001 | AMF 2001 |
Generator Voltages | ● | ● |
Generator Currents | ● | ● |
Generator Frequency | ● | ● |
Generator Apparent power (Kva) | ● | ● |
Generator Active power (Kw) | ● | ● |
Generator Reactive power (kVAr) | ● | ● |
Generator Power factor | ● | ● |
Engine Speed RPM | ● | ● |
Engine Coolant temperature | ● | ● |
Engine Oil pressure | ● | ● |
Fuel level (%) | ● | ● |
Battery voltage | ● | ● |
Battery charge alternator voltage | ● | ● |
High/Low Voltage Protection | ● | ● |
High/Low Frequency Protection | ● | ● |
Over Load Protection | ● | ● |
Short-circuit Proteciion | ● | ● |
Over Speed Protection | ● | ● |
High Coolant Temp. Protection | ● | ● |
Low Oil Pressure Protection | ● | ● |
High/Low Battery Voltage Protection | ● | ● |
Total Running Hours Counter | ● | ● |
Total Starting Times Counter | ● | ● |
Total Power kWh | ● | ● |
Total Power kWArh | ● | ● |
Cummunications by RS232/485 | ● | ● |
Remote Monitor by PC Software | ● | ● |
Remote Start | ● | ● |
Auto Mains Failure Start | ● | |
Mains Voltages | ● | |
Mains Frequency | ● |